Language select

Česky English Slovensky

Sonel MPI-505

MPI-505 meter allows measurement of short-circuit loop parameters, testing of AC and A type residual current circuit breakers and measurement of insulation resistance.

Further product information.

- Measurement of short-circuit loop parameters:

  • in L-PE, L-N, L-L circuits as well as in L-PE (RCD) circuits
  • without tripping RCD breakers of current 30 mA.
  • impedance measurement of short-circuit loops in power networks of nominal voltages: 115/200 V, 220/380 V, 230/400 V, 240/415 V and frequencies in the range of 45...65 Hz.

- Testing of AC and A types residual current circuit breakers:

  • testing of regular and selective residual current circuit breakers of nominal differential currents: 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 1000 mA,
  • IA trip current measurement,
  • tA trip time measurement for 0.5In, In, 2In, 5In,
  • measurement of earth continuity and touch voltage without tripping RCDs,
  • functionality of automatic measurement of residual current circuit breaker parameters.

- Measurement of insulation resistance at voltages: 100 V, 250 V, 500 V and 1000 V.
- Low-voltage measurement of resistance, protective connections and equipotential bonding:

  • measurement of continuity of protective connections with current 200 mA,
  • automatic calibration of test leads - capability of using any test leads,
  • measurement of resistance with low current and acoustic signaling.

- Quick verification of correctness of the PE wire connection with a touch probe.
- Measurement of AC voltage.
- Indication of phase sequence.
- Memory of 990 measurements, data transfer to a PC over the USB interface.

Request

Your request

Did you fail to find the information you were looking for, or do you have a specific request concerning this particular product?
Fill in our request form and we will contact you as soon as possible.







MPI-505
Sonel

Datasheet